中国电力教育大学院(校)长联席会
加入收藏 | 联系我们 | 后台管理
联席会学术论文专栏
联席会学术论文专栏 ·首页 > 联席会学术论文专栏
风电接入对继电保护的影响(三)——风电场送出变压器保护性能分析(2013年第3期)
类别:联席会学术论文专栏 发布时间:[2014-06-16] 点击数:911

张保会1,王  进1,郝治国1,莫莉花1,闫  凯1,王小立1,2
(1. 西安交通大学 电气工程学院,陕西 西安 710049;2. 宁夏电力公司调度中心,宁夏 银川 750001)

摘要: 仿真分析发现双馈式风电机组低电压穿越期间的短路电流频率随故障前工况偏移工频。当变压器内部故障时,基于相量值的差动与制动电流将大范围波动,基于采样值的差动保护在某些采样点动作条件不满足,差动保护均无法准确稳定地动作。以某地区实际风电接入为例,在EMTDC 平台上对风电场主变压器以及风电集群再升压变压器保护进行离线动作性能测试分析,结果表明,基于相量值及基于采样值的差动保护均无法保证快速动作,风电机组类型、运行工况、故障位置、故障类型及短路容量比是影响风电场送出变压器保护正确动作的因素。
关键词: 低电压穿越; 双馈式风电机; 风电场; 送出变压器; 差动保护; 继电保护; 变压器

Impact of wind farm integration on relay protection(3):
performance analysis for wind farm outgoing transformer protection

ZHANG Baohui1,WANG Jin1,HAO Zhiguo1,MO Lihua1,YAN Kai1,WANG Xiaoli1,2
(1. Xi’an Jiaotong University,Xi’an 710049,China;2. Dispatch Center of Ningxia Electric Power Company,Yinchuan 750001,China)


Abstract: Simulative analysis shows that the short circuit current frequency of doubly-fed induction generator during low-voltage ride-through period deviates from the fundamental frequency according to the working conditions before the fault. When the transformer internal fault occurs,the differential action and braking currents of differential protection based on phasor values fluctuate widely and the action conditions of differential protection based on sample values are not satisfied at certain sampling points,resulting in the incorrect and instable operations. With an actual regional wind farm as an example,the off-line action performance of the main transformer protection of wind farm and the step-up transformer protection of wind power group is tested and analyzed on EMTDC platform,which shows that,the fast action of differential protection based on either phasor or sample values can not be ensured and the factors influencing the accurate operation of protections for wind farm outgoing transformers are generator type,operating condition,fault location,fault type and short circuit capacity ratio.
Key words: low-voltage ride-through; doubly-fed induction generator; wind farms; outgoing transformer;differential protection; relay protection; electric transformers

点击原文:风电接入对继电保护的影响(三)——风电场送出变压器保护性能分析(2013年第3期).pdf

 

上一条:风电接入对继电保护的影响(二)——双馈式风电场电磁暂态等值建模研究(2013年第2期)
下一条:风电接入对继电保护的影响(四)——风电场送出线路保护性能分析(2013年第4期)
版权所有:中国电力教育大学院(校)长联席会
南京高新技术产业开发区星火路8号《电力自动化设备》杂志社 邮编:210032
工作电话:025-51859279,83537347 传真:025-83537349
苏ICP备10229478号 网站技术支持:光芒科技有限公司